Roth Touchline® SL

- room thermostats, sensors and WiFi module

A solution for every need

Explore the full range of Roth Touchline® SL room thermostats and sensors and discover their key features in the overview below. Did you know about our Roth Touchline® SL "Upgrade to New" concept? It allows you to easily replace old thermal actuators, control units, and room thermostats with Roth Touchline® SL, no matter the brand of the existing system.
 

Roth Touchline® SL Standard room thermostat

Wireless. With display. The temperature is easily set via touch buttons. The thermostat is also equipped with a humidity sensor so that humidity (RF) can be read in the room thermostat display.
HxLxW: 84 x 84 x 16 mm.

HVAC No. 7466397180 - White model
HVAC No. 7466397181 - Black model
 

Roth Touchline® SL Plus room thermostat

Wireless with large display. The temperature is easily set via touch buttons. Humidity sensor so that humidity (RF) can be read in the room display.
HxLxW: 84 x 84 x 24 mm.

HVAC No. 7466397190 - Battery Powered 
HVAC No. 7466397194 - 230V Mains Powered
 

Roth Touchline® SL room sensor Mini with moisture sensor

White sensor without buttons and display. The front is glossy white. The sensor measures the actual temperature in the room. Temperature and settings are easily read/changed via the display on the control unit or via the app. The relative humidity is read either via the display on the control unit or via the app.
HxLxW: 37 x 37 x 16mm

HVAC No. 7466397560
 

Roth Touchline® SL room thermostat X

Wireless, prolonged battery life (4 years), immunity to interference, easy settings with physical buttons, access advanced features via the menu.


HVAC No. 7466397170 - White model
HVAC No. 7466397171 - Black model

 

Roth Touchline® SL WiFi-module


Wireless control and monitoring of the system via the Internet. Up to 30 m indoor range.
Note: Old controllers are not compatible with new WiFi module.
HxLxW: 98 x 96 x 31 mm

HVAC No.  7466397002
 

Roth Touchline® SL Additional Module Relay

A potential-free wireless device turning a heating device/ pump on/off after receiving a message from the Master controller. Up to 6 modules can be registered to each controller (master and extensions).

HVAC No. 17TE1000.231

Roth Touchline® SL room thermostat IR

The thermostat has an integrated infrared (IR) floorsensor to control the comfort temperature on your floor. The thermostat is also equipped with a humidity sensor to monitor the humidity in the room.

HVAC no. 7466397160 - White model
HVAC no. 7466397161 - Black model

 

Roth Touchline® SL room sensor


White sensor without buttons and display.
Easy temperature control via the Roth Touchline® SL app or from the control unit.
HxLxW: 80 x 80 x 17 mm.

HVAC No. 7455397580

 

Roth Touchline® SL app
  • Total control of underfloor heating or cooling and radiator systems in all connected rooms
  • Monitoring of pump status and de-energized relay
  • Quick switching between the different operating programs
  • Easy programming
  • Control and monitoring of window switches, radiator motors and outdoor sensors
  • Statistics display with the option of monitoring temperature fluctuations
  • Voice control compatible with Google Home and Alexa

Downloads - Get more information in our datasheets, installations and brochures

Roth Touchline® SLError codeDescriptionAction
Roth Touchline® SL Plus room thermostat"UnA"When the temperature cannot be setRegister the thermostat
 "Err"When registration failedTry to register again
 "err"When an error occurred during calibrationTry to calibrate again – don’t touch the front of the thermostat while calibrating
 "--.-%"When the humidity sensor is damagedThermostat must be replaced
 "--.-*" When the temperature sensor is damagedThermostat must be replaced
    
Roth Touchline® SL standard thermostat"UnA"When the temperature cannot be setRegister the thermostat
 "Err"When registration failedTry to register again
 "err"When an error occurred during calibrationTry to calibrate again – don’t touch the front of the thermostat while calibrating
 "--.-%"When the humidity sensor is damagedThermostat must be replaced
 "--.-*" When the temperature sensor is damagedThermostat must be replaced
 "lo" + “bAt”The battery level is below 10%Change battery within shortly
    
Roth Touchline® SL Radiator actuator
 
EO1Calibration error 1
Piston retraction to mounting position took too long
Locked/damaged actuator piston.
Check the assembly and recalibrate the actuator
(Errors are displayed on the Master controller)
These errors are displayed with other information:
 - Error number
 - Actuator number, zone number,
 - Time of occurrence

Example:
Error 2
Actuator 3 - Zone 6
Time for occurrence: 26 min.
EO2Calibration error 2
Piston max. extended as it did not meet any resistance during calibration
 - Actuator is not properly/fully screwed onto the valve
 - Actuator movement was excessive, or a non-proprietary valve was found
 - Motor load measurement failure occurred.
Check the assembly and recalibrate the actuator
 EO3Calibration error 3
Piston extension to short. The piston meet resistance too early during the calibration
 - Actuator movement was too small, or a non-proprietary valve was found
 - Motor load measurement failure occurred.
 - Motor load measurement inaccurate due to low battery level (check level on controller)
Check the assembly and recalibrate the actuator
 EO4Actuator feedback communication error
For the last “X” minutes, the actuator did not receive a data package via wireless communication
After this error is triggered, the actuator will set itself to 0% open
The error will be reset when a data package is received
 - Master controller switched off
 - Poor or no signal originating from controller
 - Defective radio communication module in the actuator
 EO5Battery low
The actuator will detect battery replacement after voltage rises and launch calibration
 - Change all batteries
 EO6Not in use 
 EO7Actuator blocked - While changing the opening of the valve, excessive load was encountered.
Recalibrate the actuator
    
Roth Touchline® SL Window contact
(Errors are displayed on the Master controller)
No communication Window sen. “X” - Zone “X”
Time for occurrence: “X”
Example: “No communication Window sen. 1 - Zone 2
Time of occurrence 2 min.”

This information will indicate which window-opening sensor (1 to 6) in which zone (1 to 48) has reported a communication error, and how long this error has been active.
Possible two reasons:
1 -run out of battery -> change the battery
2 -poor radio connection to controller.
To improve this, use a 5 m antenna extender cable (sold separately), and place the antenna closer to the sensor, which is having communication problems.
If the main device is mounted in a metal cabinet, then place the antenna outside this cabinet.

Optionally, use a signal repeater (Roth Touchline® SL repeater).
    
Roth Touchline® SL Outdoor sensor
(Errors are displayed on the Master controller)
No communication External sensor
Time for occurrence: “X”
This information will indicate that Outdoor temperature sensor has reported a communication error, and how long this error has been active.Possible two reasons:
1 -run out of battery -> change the battery
2 -poor radio connection to controller.
To improve this, use a 5 m antenna extender cable (sold separately), and place the antenna closer to the sensor, which is having communication problems.
If the main device is mounted in a metal cabinet, then place the antenna outside this cabinet.

Optionally, use a signal repeater (Roth Touchline® SL repeater).
 Sensor damaged External sensor
Time for occurrence: “X”
This information will indicate that Outdoor temperature sensor is damaged, and how long this error has been active.Outdoor sensor must be replaced
    
Roth Touchline® SL 8ch Master Controller 8ch and SL 8ch Extension Controller
(other errors which are displayed on the Master and Extension controller)
No communication
Actuator “X” - Zone “X”
Time for occurrence: “X”
This information will indicate which radiator actuator (1 to 6) in a given zone (1 to 48) has reported a communication error, and how long this error has been active.Possible two reasons:
1 -run out of battery -> change the battery
2 -poor radio connection to controller.
To improve this, use a 5 m antenna extender cable (sold separately), and place the antenna closer to the sensor, which is having communication problems.
If the main device is mounted in a metal cabinet, then place the antenna outside this cabinet.

Optionally, use a signal repeater (Roth Touchline® SL repeater).
 No communication
Room sensor - Zone “X”
Time for occurrence: “X”
This information will indicate that a room thermosatat or temperature sensor in a given zone (1 to 48) has reported a communication error, and how long this error has been active.Possible two reasons:
1 -run out of battery -> change the battery
2 -poor radio connection to controller.
To improve this, use a 5 m antenna extender cable (sold separately), and place the antenna closer to the sensor, which is having communication problems.
If the main device is mounted in a metal cabinet, then place the antenna outside this cabinet.

Optionally, use a signal repeater (Roth Touchline® SL repeater).
 No communication
Floor sensor - Zone “X”
Time for occurrence: “X”
This information will indicate that a floor temperature sensor in a given zone (1 to 48) has reported a communication error, and how long this error has been active.Possible three reasons:
1 -run out of battery -> change the battery
2 -poor radio connection to controller.
To improve this, use a 5 m antenna extender cable (sold separately), and place the antenna closer to the sensor, which is having communication problems.
If the main device is mounted in a metal cabinet, then place the antenna outside this cabinet.

Optionally, use a signal repeater (Roth Touchline® SL repeater).

3 - Place sensor/room thermostat in a different place – closer to the controller.
 No communication
Additional c. - Master mo. / “X”. Extens.
Time for occurrence: “X”
This information will indicate lost connection between Master module and Extension modules, and how long this error has been activeIf it is wireless connection (radio connection) – to improve communication if it is long distance between devices use 5 m antenna extender cable (sold separately).

Optionally, use a signal repeater (Roth Touchline® SL repeater).

If it is cable connection:
 - Check cable and connectors
 - Check mains 230V power connection cable
 Sensor damaged
Floor sensor - Zone “X”
Time for occurrence: “X”
Floor temperature sensor broken or disconnected a given in zone (1 to 48) has reported a communication error, and how long this error has been active.Check the connection cable / replace the sensor
 Sensor damaged
Room sensor - Zone “X”
Time for occurrence: “X”
Room temperature sensor/room thermostat is damaged in a given zone (1 to 48) has reported a communication error, and how long this error has been active.Replace sensor/room thermostat
 No communication 
“X” Extension 8ch / Master module
Time for occurrence: “X”
This information will indicate lost connection between a specific extension controller (nr 1 to nr 3) and the master controller, and how long this error has been active.If it is wireless connection (radio connection) – to improve communication if it is long distance between devices use 5 m antenna extender cable (sold separately).

Optionally, use a signal repeater (Roth Touchline® SL repeater).

If it is cable connection:
 - Check cable and connectors
 - Check mains 230V power connection cable
 No communication
Extension 4 c. - Master mo. / “X”. Extens.
Time for occurrence: “X”
This message occurs when there is a communication error between the Master 8ch controller and connected 4ch module or extension 8ch controller number 1, 2 or 3 with connected 4 ch module, and how long this error has been active. - Check connection cable between 8 ch controller and 4 ch module
 - Check mains 230V power cable in 4 ch module
 - Connect again and register again 4 ch module
 No communication
Internet mod. - Master mo.
Time for occurrence: “X”
Communication with master controller has been lost due to damaged cable / power loss. - Check connection cable
 - Connect again with different cable and check
 System version out of date
“X” Extension 8ch / Master module
Time for occurrence: “X”
This information will show which device (Master 8 ch controller or 8 ch Extension controller nr 1 to nr 3) has a firmware  version out of date, and how long this error has been active.The error occurs when one of the devices in the entire system has an older firmware version. When such an error occurs, some new features of the system may not work. To fix it - upload the latest firmware to all devices in the kit: 8 ch master controller, 8 ch extension controller and 4 ch module. Same file with the latest firmware is used to update all the above-mentioned devices.
 Software version incorrect
“X” Extension 8ch / Master module
Time for occurrence: “X”
This information will show which device (Master 8ch controller or 8 ch Extension controller nr 1 to nr 3) has incompatible firmware version, and how long this error has been active.The error occurs when one of the devices in the entire system has an older firmware version. The system will not work properly - the latest firmware should be uploaded to all devices straight away. A device with an old firmware version in this case will not register to the Master controller - all devices must be updated to the same firmware version before registration.
 No communication
OpenTherm - Master module
Time for occurrence: “X”
OpenTherm communication has been lost due to damaged cable / power loss. - Check mains 230V power / connection cable.
 - OpenTherm communication is enabled and nothing is connected.
 - OpenTherm device is switched off or is faulty.
    
Roth Touchline® SL Controller 4 ch WiFiNo communication
Actuator “X” - Zone “X”
Time for occurrence: “X”
This information will indicate which radiator actuator (1 to 6) in a given zone has reported a communication error, and how long this error has been active.Possible two reasons:
1 -run out of battery -> change the battery
2 -poor radio connection to controller.
To improve this, use a 5 m antenna extender cable (sold separately), and place the antenna closer to the sensor, which is having communication problems.
If the main device is mounted in a metal cabinet, then place the antenna outside this cabinet.

Optionally, use a signal repeater (Roth Touchline® SL repeater).
 No communication
Room sensor - Zone “X”
Time for occurrence: “X”
This information will indicate that a room thermostat or temperature sensor in a given zone has reported a communication error, and how long this error has been active.Possible two reasons:
1 -run out of battery -> change the battery
2 -poor radio connection to controller.
To improve this, use a 5 m antenna extender cable (sold separately), and place the antenna closer to the sensor, which is having communication problems.
If the main device is mounted in a metal cabinet, then place the antenna outside this cabinet.

Optionally, use a signal repeater (Roth Touchline® SL repeater).
 No communication
Floor sensor - Zone “X”
Time for occurrence: “X”
This information will indicate that a floor temperature sensor in a given zone has reported a communication error, and how long this error has been active.Possible three reasons:
1 -run out of battery -> change the battery
2 -poor radio connection to controller.
To improve this, use a 5 m antenna extender cable (sold separately), and place the antenna closer to the sensor, which is having communication problems.
If the main device is mounted in a metal cabinet, then place the antenna outside this cabinet.

Optionally, use a signal repeater (Roth Touchline® SL repeater).

3 - Place sensor/room thermostat in a different place – closer to the controller.
 Sensor damaged
Floor sensor - Zone “X”
Time for occurrence: “X”
Floor temperature sensor broken or disconnected a given in zone has reported a communication error, and how long this error has been active.Check the connection cable / replace the sensor
 Sensor damaged
Room sensor - Zone “X”
Time for occurrence: “X”
Room temperature sensor/room thermostat is damaged in a given zone  has reported a communication error, and how long this error has been active.Replace sensor/room thermostat

Do you want to know more about our products?

Disclaimer

We have recently learned that data traffic on the LTE800 bandwidth (e.g., 5G in mountains and/or in long-distance areas) may cause issues related to blocking of radio signals sent internally between Roth’s wireless products if the masts are too close or if the signal strength is too high.
Further, we cannot completely exclude the possibility that the installation or implementation of radio-based technologies in the future may cause similar issues.

All of the aforementioned issues are in all cases caused by conditions beyond Roth’s control. Roth can thus not be held liable for, or acknowledge claims attributable to, any such interruptions caused by installations (etc.) carried out by third parties beyond Roth’s control.